Drop In Fire Collar
-
Allproof Drop in fire collars provide a simple and effective passive fire rating option for thin concrete floors or trapezoidal steel tray concrete floors. These floors feature profile changes on the underside of the slab and make it difficult to fire rate with a conventional fire collar fixed to the underside of a floor slab.
Full Brochure
40mm
50mm
65mm
80mm
100mm
150mm
Extendable 40mm
Extendable 50mm
Extendable 65mm
Extendable 80mm
Extendable 100mm
Standard
Code Description .pfd File CAD File DIFC40 40mm Allproof Drop In Fire Collar
 DIFC40.pdf(307 KB)
 DIFC40.dwg(244 KB)DIFC50 50mm Allproof Drop In Fire Collar
 DIFC50.pdf(317 KB)
 DIFC50.dwg(263 KB)DIFC65 65mm Allproof Drop In Fire Collar
 DIFC65.pdf(302 KB)
 DIFC65.dwg(252 KB)DIFC80 80mm Allproof Drop In Fire Collar
 DIFC80.pdf(309 KB)
 DIFC80.dwg(267 KB)DIFC100 100mm Allproof Drop In Fire Collar
 DIFC100.pdf(312 KB)
 DIFC100.dwg(277 KB)DIFC150 150mm Allproof Drop In Fire Collar
 DIFC150.pdf(357 KB)
 DIFC150.dwg(380 KB)
Extendable 210
Code Description .pfd File CAD File DIFC40X210 40mm Allproof Drop In Fire Collar Extendable up to 210mm
 DIFC40X210.pdf(137 KB)
 DIFC40X210.dwg(367 KB)DIFC50X210 50mm Allproof Drop In Fire Collar Extendable up to 210mm
 DIFC50X210.pdf(140 KB)
 DIFC50X210.dwg(162 KB)DIFC65X210 65mm Allproof Drop In Fire Collar Extendable up to 210mm
 DIFC65X210.pdf(142 KB)
 DIFC65X210.dwg(169 KB)DIFC80X210 80mm Allproof Drop In Fire Collar Extendable up to 210mm
 DIFC80X210.pdf(148 KB)
 DIFC80X210.dwg(171 KB)DIFC100X210 100mm Allproof Drop In Fire Collar Extendable up to 210mm
 DIFC100X210.pdf(149 KB)
 DIFC100X210.dwg(186 KB)
Suitable For Fitting With:
- Thin concrete floors (minimum 70mm)
- Trapezoidal steel tray concrete floors (composite floors)
Features:
- Installed and fixed from top side of slab
- Can be retrofit around pipe
- Made from Galvanised steel
Installation Instructions:
- Core drill hole to specified diameter to suit pipe size.
-
Install drop in fire collar fixing with two metal pin anchors. (Floor waste installs require the tabs to be recessed into the slab).
-
Ensure collar on underside of slab is exposed no greater than 80mm and recessed in slab no more than 5mm.
- Insert pipework through collar.
- Seal gaps between concrete/collar and collar/pipe with 15mm depth of Allproof MAS310 or Bostik Fireban One intumescent sealant.
-
Allproof recommends any thermal or acoustic lagging maintains a 50mm separation to the fire collar.
For test results please see our Fire Brochure literature.
 Fire-Penetration-Schedule.xlsx(13 KB)
Composite Floor Installation Details:
Flat Slab Installation Details:
Composite Floor Waste Floor Installation Details:
Flat Slab Floor Waste Installation Details: